Supply | |
---|---|
Connection | backplane bus |
Rated voltage | 5 V DC , only in connection with the power supplies FB92** |
Power consumption | 2 W |
Auxiliary energy | 24 V DC Trunk load 20 mA |
Fieldbus interface | |
Fieldbus type | FOUNDATION Fieldbus H1 |
FOUNDATION Fieldbus | |
Station connection | directly at the trunk or via spur protector |
Number of stations per bus line | 1 or 2, depending on the required response times |
Number of channels per station | max. 20 analog, max. 40 digital |
Supported I/O modules | 5 slots, to be filled with (combinations possible): 1*08 digital input, 8-channel, NAMUR 3*05 analog input, 4-channel, 20 mA (HART via service bus) 4*05 analog output, 4-channel, 20 mA (HART via service bus) 5204 Pt100 RTD input, 4-channel 5205 thermocouple input, 4-channel 6305 relay output, 4-channel, 230 V 6306 relay output, 8-channel, 24 V 6*08 digital output, 8-channel, Ex i 6210-6215 digital output, 4-channel, Ex i power * = variable (2=IS, 3=Ex e) |
Bus length | max. 1900 m (must not be exceeded by the sum of all trunk and spur lines) |
Spur length | max. 120 m (depending on the number of field devices. Modular I/O station = 1 field device) |
Addressing | via PCS (software) |
Internal bus | |
Connection | backplane bus |
Indicators/settings | |
LED indicator | LED green (power supply): On = operating, fast flash = cold start LED red (collective alarm): On = internal fault, flashing = no fieldbus LED yellow (operating mode): Flashing = active |
Directive conformity | |
Electromagnetic compatibility | |
Conformity | |
Electromagnetic compatibility | NE 21 |
Degree of protection | IEC 60529 |
Ambient conditions | |
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) |
Storage temperature | -25 ... 85 °C (-13 ... 185 °F) |
Relative humidity | 95 % non-condensing |
Shock resistance | shock type I, shock duration 11 ms, shock amplitude 15 g, number of shocks 18 |
Vibration resistance | frequency range 10 ... 150 Hz; transition frequency: 57.56 Hz, amplitude/acceleration ± 0.075 mm/1 g; 10 cycles frequency range 5 ... 100 Hz; transition frequency: 13.2 Hz amplitude/acceleration ± 1 mm/0.7 g; 90 minutes at each resonance |
Damaging gas | designed for operation in environmental conditions acc. to ISA-S71.04-1985, severity level G3 |
Mechanical specifications | |
Degree of protection | IP20 (module) , a separate housing is required acc. to the system description |
Connection | via backplane |
Mass | approx. 750 g |
Dimensions | 57 x 107 x 132 mm (2.2 x 4.2 x 5.2 inch) |
Data for application in connection with hazardous areas | |
EU-Type Examination Certificate | PTB 97 ATEX 1074 U |
Directive conformity | |
International approvals | |
ATEX approval | PTB 97 ATEX 1075 |
EAC approval | Russia: RU C-IT.MIII06.B.00129 |
Marine approval |