Supply | |
---|---|
Connection | X20: terminals 3, 5 (+); 4, 6 (-) |
Nominal voltage | 24 V DC , in consideration of rated voltage of used isolators |
Voltage drop | 0.9 V , voltage drop across the series diode on the termination board must be considered |
Ripple | ? 10 % |
Fusing | 4 A , in each case for 16 modules |
Power dissipation | ? 500 mW , without modules |
Reverse polarity protection | yes |
Redundancy | |
Supply | Redundancy available. The supply for the isolators is decoupled, monitored and fused. |
Fault indication output | |
Connection | X20: terminals 1, 2 |
Output type | volt-free contact |
Contact loading | 30 V DC, 1 A |
Indicators/settings | |
Display elements | LED PWR1 (termination board power supply), green LED LED PWR2 (termination board power supply), green LED LED FAULT (fault indication), red LED - LED lits: module failure - LED flashes: power supply failure |
Directive conformity | |
Electromagnetic compatibility | |
Conformity | |
Electromagnetic compatibility | NE 21:2012 For further information see system description. |
Degree of protection | IEC 60529:2001 |
Ambient conditions | |
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) |
Storage temperature | -40 ... 70 °C (-40 ... 158 °F) |
Mechanical specifications | |
Degree of protection | IP20 |
Connection | |
Core cross-section | screw terminals: 0.25 ... 1.5 mm2 (24 ... 12 AWG) |
Material | housing: polycarbonate, 10 % glass fiber reinforced |
Mass | approx. 730 g |
Dimensions | 216 x 200 x Или отправьте нам запрос наch) , height including module assembly |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 |
Data for application in connection with hazardous areas | |
EU-Type Examination Certificate | CESI 06 ATEX 022 |
Non-hazardous area | |
Certificate | DEMKO 18 ATEX 2116 X |
Galvanic isolation | |
Directive conformity | |
International approvals | |
UL approval | |
IECEx approval | |
Accessories | |
Designation | optional accessories: - HART communication board HiATB01-HART-2X16 - HART multiplexer master HiDMux2700 - HART connection cable HiACA-UNI-FLK34-*M* - label carrier HiALC-Hi*TB-SET-1** - control system specific connection cable on request |
8 (029) 555-8-000 | |
8 (044) 555-8-000 | |
8 (01 |